Code:
0437
Detection type:
linear temperature detector
Max. length of detection cable:
600 m
Number of zones:
1
Signaling:
Option to connect acoustic/optical signalling
Installation:
Wall or cabinet mounted
Monitored states:
Operation, Malfunction, Fire, Firefighting
Other features:
Pressure drop detection, signal transmission for sprinkler activation
More information
>DETECTION PART OF LOCAL FIRE EXTINGUISHING SYSTEMS (LPHS)
The detection part of local fire extinguishing systems (LPHS) is a fundamental element in fire safety technologydesigned for early detection of emerging hazardous conditions, effective localization of the fire outbreak and subsequent activation of firefighting. Thanks to its modular design and advanced diagnostic functions, the system is suitable for a wide range of applications in industrial and technological environments.
By its design, the detection system is able to detect and report the following conditions - OPERATION, FAULT, FIRE, EXTINGUISHMENT.
This detection system allows easy connection to any EPS system.
The PWG01 unit is an integral part of the local fire suppression systems (LPHS) and is used to evaluate signals from Protectowire PHSC type linear temperature detectors.
In addition to reliable fire detection, this unit offers advanced functionality - it allows approximate determination of the location of a short circuit on the detection cable, which greatly facilitates fire location in larger installations.
In addition, the PWG01 monitors the resistance of the detection loop so it can detect in time:
gradual degradation of the conductor (e.g. loss of conductivity in the joints), the formation of false conductive paths (e.g. due to moisture or dirt).
the occurrence of a fire (short circuit on the cable),
fault condition (e.g. loop breakage),
gradual degradation of the cable (loss of conductivity or formation of false conductive paths)
The extinguishing is started automatically if the detection cable detects one of the following conditions:
-
Fire - detection of a short circuit in a given part of the cable.
-
Pressure drop - the system can be connected to a pressure sensor. If the pressure drops below a set limit, fire suppression will be automatically triggered, typically by a sprinkler system.
PRODUCT FEATURES
- Power supply: 24 V DC
- Connection of one detection zone
- Monitored output for connection to audible or visual alarm
- Detection line continuity monitoring
- Relay outputs "Fire" and "Fault" for easy integration with EPS or PTZS
- Maximum length of detection cable: up to 600 metres
- Number of monitoring zones: 1 (expandable according to system configuration)
- Signalling options: acoustic, optical (optional connection)
- Communication type: galvanically isolated signals, compatible with EPS/PTZS
- Mounting: wall mounted / rack mounted
AREAS OF APPLICATION
Industrial plants and production lines, warehouses and logistics centres, data centres and server rooms, transport infrastructure (tunnels, garages), electricity substations and technical plants